Boiling and Condensation
When a fluid changes phase, it absorbs or releases its latent heat — enabling enormous heat fluxes at small temperature differences. This is why boiling and condensation power so much of thermal engineering.
This chapter treats phase-change convection: the regimes of pool boiling and the critical heat flux, flow boiling in tubes, and film and dropwise condensation — all governed by latent heat \(h_{fg}\) and surface tension.
Learning objectives
- Distinguish pool boiling, flow boiling, film condensation, and dropwise condensation from physical cues.
- Use saturation temperature, wall superheat or subcooling, and vapor quality with consistent signs.
- Select boiling and condensation correlations only within their stated geometry and regime limits.
- Evaluate phase-change properties at saturation and liquid-film properties at the specified film temperature.
- Compute heat flux, phase-change rate, quality, and condensation coefficient.
- Audit critical-heat-flux margin, units, energy balances, and physical limits.
Boiling Heat Transfer
Boiling is vapor formation at a liquid–solid interface when \(T_s>T_{\text{sat}}(p)\). It is not identified by temperature alone: pressure fixes saturation temperature, and a liquid may be locally boiling while its bulk remains subcooled. The signed wall superheat is \(\Delta T_e=T_s-T_{\text{sat}}>0\); use absolute temperature only where a correlation requires it.
Energy transport and nucleation
Each kilogram formed carries \(h_{fg}\) joules, while departing bubbles renew liquid at the wall. Active nucleation also depends on roughness, wettability, dissolved gas, and pressure; therefore a surface–fluid constant is not transferable without evidence.
Physical meaning
A large boiling coefficient does not mean the wall can accept unlimited heat. The boiling curve is non-monotonic, and the safe operating regime matters more than a single value of \(h=q''/\Delta T_e\).
Problem-solving strategy
- Identify pool versus forced-flow boiling and obtain \(T_{\text{sat}}\) at the local absolute pressure.
- Locate the likely regime from wall superheat, heat flux, and flow quality.
- Evaluate liquid/vapor properties at saturation unless the selected correlation specifies otherwise.
- Apply the minimum correlation that matches fluid, surface, geometry, and validity range.
- Audit energy conservation and compare operating heat flux with critical heat flux using a documented margin.
Pool Boiling
In pool boiling there is no imposed bulk flow. Increasing wall superheat produces natural convection, onset of nucleate boiling, vigorous nucleate boiling, critical heat flux (CHF), unstable transition boiling, a minimum-flux point, and stable film boiling. Transition boiling is generally unsuitable for controlled design because increasing wall temperature can reduce heat flux.
The Boiling Curve
Nucleate boiling combines latent transport and mixing. At CHF, vapor columns coalesce and interrupt rewetting; under imposed heat flux this can cause a sudden wall-temperature excursion. Stable film boiling has a continuous vapor layer and may require radiation as well as convection.
Strategy
Saturated liquid enters and saturated vapor leaves, so a latent-energy balance closes the problem without a boiling correlation.
Givens
- \(\dot Q=18.0\) kW, \(h_{fg}=201\) kJ/kg; steady and adiabatic except for heater input.
Physical/model interpretation
The control volume is the refrigerant. Positive heat input creates vapor; kinetic, potential, and sensible-energy changes are neglected.
Unit/sign/limit checks
Units: \(({\rm kJ/s})/({\rm kJ/kg})={\rm kg/s}\).
Signs: positive heater input gives positive vapor generation.
Limit: as \(\dot Q\to0\), \(\dot m_v\to0\); doubling power doubles production under this model.
Engineering insight
This is an energy-capacity result, not a surface-temperature prediction; area, boiling regime, CHF margin, and losses must still be checked.
The critical heat flux is the single most important number in boiling design. Operating just below it gives huge heat transfer; cross it and the surface temperature can jump by hundreds of degrees almost instantly — the "burnout" that destroys heating elements and fuel rods.
Flow Boiling
Flow boiling couples forced convection, nucleation, acceleration, and pressure drop. Equilibrium quality \(x\) is vapor mass fraction for a saturated mixture, \(0\le x\le1\); negative calculated quality denotes subcooled liquid and \(x>1\) denotes superheated vapor rather than a physical mixture quality.
Forced Convection Boiling
Local flow pattern may pass through bubbly, slug, annular, and mist regimes. A correlation must match channel size, orientation, mass flux, quality, pressure, and heat-flux range. Dryout and departure from nucleate boiling are distinct limits.
Strategy
First pay the sensible-heating requirement to saturation; assign only the remaining energy to evaporation.
Givens
- \(\dot m=0.080\) kg/s, \(\dot Q=60.0\) kW, \(T_i=90^\circ{\rm C}\), saturation properties supplied.
Physical/model interpretation
Steady, negligible losses and pressure drop; the outlet is an equilibrium saturated mixture if the computed quality lies from zero to one.
Unit/sign/limit checks
Units: kW divided by \(({\rm kg/s})({\rm kJ/kg})\) is dimensionless.
Signs: With heat into the control volume defined positive, \(60.0-3.36=56.64\) kW remains positive, so the computed quality increment must be positive; a negative result would instead indicate that the outlet remained subcooled.
Limit: \(0<x_o<1\), validating the mixture interpretation; the sensible load is only 5.6% of input.
Engineering insight
Real design must include pressure-dependent saturation temperature, axial heat flux, dryout, and two-phase pressure drop.
Condensation Heat Transfer
Condensation occurs when vapor contacts a surface below its local saturation temperature, so \(\Delta T_c=T_{\rm sat}-T_s>0\). Noncondensable gas can build a diffusion layer and drastically lower performance; pure-vapor film correlations then overpredict heat transfer.
Film vs. Dropwise
Film condensation is predictable but the growing condensate layer adds conduction resistance. Dropwise condensation repeatedly exposes surface and can be much stronger, but its durability depends on surface chemistry and contamination.
Film Condensation
Nusselt's vertical-plate result assumes steady laminar film flow, negligible vapor shear and inertia, constant properties, a pure saturated vapor, and conduction across the film. Evaluate liquid properties at \(T_f=(T_{\rm sat}+T_s)/2\), while \(h_{fg}\) comes from saturation data.
Strategy
The pure vapor, vertical geometry, and supplied film properties cue the laminar Nusselt plate model.
Givens
- \(L=0.60\) m, \(W=0.30\) m, \(\Delta T_c=10\) K, \(A=WL\); properties supplied at \(T_f=55^\circ{\rm C}\).
Physical/model interpretation
Gravity drives a downward film. Heat and condensate rates are reported positive from vapor to wall; edge effects and vapor shear are neglected.
Unit/sign/limit checks
Units: \(hA\Delta T\) gives W and W/(J/kg) gives kg/s.
Signs: \(T_{\rm sat}>T_s\), so heat flows to the wall and condensation is positive.
Limit: the correlation gives \(h\propto(\Delta T_cL)^{-1/4}\), while \(\dot Q\propto\Delta T_c^{3/4}\), so zero subcooling gives zero heat rate despite divergent idealized \(h\).
Engineering insight
Verify film Reynolds number and remove air leakage before sizing; noncondensables can dominate the resistance.
Film Condensation Inside Horizontal Tubes
Inside horizontal tubes, gravity drains liquid around the circumference while vapor shear redistributes it. The Chato form is a low-vapor-velocity model; at higher mass flux use a validated internal-condensation correlation that includes quality, shear, and flow regime.
Dropwise Condensation
Dropwise condensation may greatly outperform film condensation because droplets depart and renew the surface. It should not be credited as a permanent design condition unless coating life, fouling, chemistry, and inspection have been demonstrated.
Chapter recap
- Recognize the regime before selecting a correlation.
- Anchor properties to saturation pressure and film temperature.
- Use an energy balance for phase rate or quality before adding local heat-transfer detail.
- Treat CHF, dryout, noncondensables, and coating durability as engineering limits.
Before moving on
You should be able to sketch the boiling curve, calculate quality and condensate rate, state each correlation's assumptions, and audit units, signs, and regime validity.