Internal Forced Convection
Internal convection is governed by confinement: velocity and temperature profiles develop from the inlet until the walls control the entire cross-section.
A sound solution joins a bulk-flow energy balance to a regime- and boundary-condition-specific correlation, while pressure drop supplies the hydraulic cost.
Learning objectives
- Define mean velocity, bulk mean temperature, and hydraulic diameter physically.
- Distinguish hydrodynamic and thermal development and test entry-length assumptions.
- Select laminar or turbulent correlations by Reynolds number, wall condition, and validity range.
- Predict outlet temperature, wall temperature, heat rate, pressure drop, and pumping power.
- Audit property temperatures, signs, dimensions, and limiting behavior.
Introduction
Internal flow is driven through a closed passage. For noncircular ducts use \(D_h=4A_c/P_w\), where \(P_w\) is wetted perimeter. The hydraulic diameter transfers established duct correlations; it does not make every noncircular velocity profile identical to a circular one.
Problem-solving strategy
- Identify passage geometry, wetted perimeter, wall thermal condition, and desired thermal and hydraulic outputs.
- Estimate a representative bulk temperature, evaluate properties there, and evaluate wall viscosity separately if the correlation requires it.
- Compute \(D_h\), \(V_m\), \(Re\), \(Pr\), and entry lengths.
- Select a correlation matching regime, development, geometry, roughness, and heating or cooling.
- Couple \(h\) to the bulk energy balance and audit units, directions, range limits, and pumping cost.
Mean Velocity and Mean Temperature
The mean velocity preserves mass flow. Bulk mean temperature preserves enthalpy flow: for nearly constant \(c_p\), \(\dot m c_pT_m=\int_A\rho u c_pT\,dA\). It is not generally the arithmetic area-average temperature because faster fluid carries more energy.
Driving temperature
Local convection uses \(q_s''=h_x(T_s-T_m)\). The wall-to-bulk difference, not wall-to-centerline or wall-to-inlet difference, is the thermodynamic driving force at a section.
Physical meaning
As the fluid is heated, \(T_m\) rises downstream and the available wall-to-fluid temperature difference may shrink. Constant heat flux and constant wall temperature therefore produce different temperature histories and different fully developed Nusselt constants.
The Entrance Region
Hydrodynamically developed means the normalized velocity profile no longer changes with \(x\); thermally developed means the normalized temperature-profile shape no longer changes. It does not mean velocity or bulk temperature is spatially constant.
General Thermal Analysis
For steady flow with negligible kinetic and potential energy changes and no shaft work within the heated section, \(\dot Q=\dot m c_p(T_o-T_i)\). Constant heat flux makes \(T_m(x)\) linear when properties are constant; a constant wall temperature produces exponential approach and can never be crossed by the fluid in this model.
Strategy
Uniform heat flux gives a direct energy balance; the fully developed laminar constant-flux value \(Nu=4.36\) then fixes wall-to-bulk difference.
Givens
- \(D=0.025\) m, \(L=3.0\) m, \(q_s''=4000\) W/m², \(\dot m=0.080\) kg/s.
- \(T_i=25^\circ\)C, \(c_p=2100\) J/kgK, \(k=0.145\) W/mK.
Physical/model interpretation
Steady, single-phase, constant properties, negligible axial conduction and heat loss; positive heat enters the oil.
Unit/sign/limit checks
Units: W divided by kg/s·J/kgK gives K; W/m² divided by W/m²K gives K.
Signs: Positive flux raises both bulk and wall temperature.
Limit: The high wall temperature follows from oil's low \(h\); if \(q_s''\to0\), both temperature rises vanish.
Engineering insight
The mild bulk rise hides a severe wall temperature. Real approval requires checking oil degradation, property variation, heater limits, and whether fully developed conditions actually exist.
Strategy
The fixed wall temperature and known average \(h\) call for the exponential bulk-temperature relation, followed by the fluid energy balance.
Givens
- \(T_s=80^\circ\)C, \(T_i=20^\circ\)C, \(D=0.018\) m, \(L=2.0\) m.
- \(\dot m=0.120\) kg/s, \(h=900\) W/m²K, \(c_p=4180\) J/kgK.
Physical/model interpretation
Steady single-phase heating, constant properties and wall temperature, negligible external loss. Heat into water is positive.
Unit/sign/limit checks
Units: \(hA/(\dot mc_p)\) is dimensionless and capacity rate times kelvin is W.
Signs: \(20 Limit: As \(L\to\infty\), the exponential tends to zero and \(T_o\to T_s\) without crossing it.
Engineering insight
Doubling area does not double heat indefinitely because the driving temperature shrinks downstream; the exponential model makes that diminishing return explicit.
Laminar Flow in Tubes
Exact fully developed circular-tube solutions give \(Nu=3.66\) for uniform wall temperature and \(Nu=4.36\) for uniform wall heat flux. These constants require both the stated boundary condition and thermal development. Developing laminar flow usually has a larger average coefficient and requires an entrance correlation, often with a wall-to-bulk viscosity correction.
Turbulent Flow in Tubes
Turbulent mixing raises heat transfer and pressure loss. Dittus–Boelter is convenient for smooth, fully developed flow with modest property variation; Gnielinski covers a broader range and links \(Nu\) to friction factor. Roughness, strong viscosity changes, transition, or short tubes require a more suitable model.
Strategy
Check turbulent and length criteria, use Dittus–Boelter with the cooling exponent, then use a consistent Darcy friction factor for hydraulic cost.
Givens
- \(V=2.0\) m/s, \(D=0.030\) m, \(L=12\) m; smooth tube.
- Bulk properties supplied; fluid is being cooled, so \(n=0.3\).
Physical/model interpretation
Steady, incompressible, fully developed turbulent flow; fittings and elevation excluded. Pressure decreases in the flow direction.
Unit/sign/limit checks
Units: In Darcy–Weisbach, dimensionless \(f_D(L/D)\) multiplies \(\rho V^2/2\), whose units are kg/(m·s²) = Pa. Then \(\dot V\Delta P\) has units m³/s·Pa = J/s = W, confirming both reported quantities.
Signs: Reported \(\Delta P=15.3\) kPa is a positive loss; static pressure drops along flow.
Limit: The valid \(Re\), \(Pr\), and \(L/D\) support the correlation; pump shaft power must exceed 21.6 W.
Engineering insight
A complete loop design adds fittings, roughness, elevation, pump efficiency, fouling, and allowable erosion velocity; this calculation isolates only straight-tube behavior.
Chapter recap
- Bulk quantities preserve mass and energy flow through nonuniform profiles.
- Regime, entry length, geometry, wall condition, and property temperature control correlation selection.
- Energy balances determine bulk-temperature change; correlations determine wall-to-bulk behavior.
- Before moving on, be able to compute \(D_h\), \(Re\), entry lengths, \(Nu\), outlet temperature, pressure loss, and a specific audit.